Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM03178
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/30/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000*1.) HAVE UNIT NUMBER ADDED TO PERMIT 2.) OK WALL & CEILING ROUGH ELECT. | |
| 07/26/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) PLEASE HAVE UNIT #ADDED TO INSPECTION CARD. 2.) NEED FHA STRAPS 3.) USE ROMEX CONNECTOR AS PER LISTING AT PANEL. 4.) NEED ACCESSABILITY FOR SPLICES W KITCHEN CEILING. 5.) NEED TO SECURE ROMEX TO BOXES 373-5 (C) EXH FANS. |