Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/21/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 05/16/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OK ROUGH ELECTRIC |
| 05/14/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) GROUND WIRE TO BE 3/4 WRAP UNDER SCREWS IN A CLOCKWISE DIRECTION AND NO MORE THAN 3/4 OF A TURN. 2.) PROTECT EXPOSED CABLE ACCROSS THE FLOOR 3.) PLEASE GROUND AL METAL BOXES 4.) REPLACE MISSING CABLE CLAMPS ON 4/0 BOXES 370-17 AND TIGHTEN 5.) PROTECT CABLE ENTER IN FLEX CONDUIT 300-4. 6.) FINISH WIRING CASTIA WHAT IS OF WIRE HANGING FOR ? |
| 05/01/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) PROTECT CABLE ACCROSS THE FLOOR OK WALLS ROUGH ELECTRIC. |