Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/28/2001 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 07/10/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) ALL OUTSIDE OUTLETS SHOULD BE GFCI 2) OUTLET AT KITCHEN IS NOT WORKING PROPERLY 3) OUTLET AT KITCHEN HOT IS REVERSED 4) OUTLET IN DINNING AREA OPEN GROUND 5) ELECTRIC COOLER NEEDS TO BE HOOKED UP 6) THERMASTAT FOR UNDER SLAB HEATING SYSTEM 7) PROVIDE GFCI OUTLET AT PENNINSULA 8) PROVIDE CONDENSATION PIPE FOR PRESSURE RELEAVE VALVE AT WATER HEATER |