Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T01CM03133
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/12/2001 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
07/11/2001 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245*1.) SUPPORT MC CABLE PER 334-10 N.E.C 2.) SUPPORT BOXES EMT. PER 348-13 370-23, 300-11, 3.) CANNOT USE RACEWAYS TO SUPPORT RACEWAYS. 4.) A RE-INSPECTION IF NOT IN COMPLIANCE BASED ON PREVIOUS JOBS WITH THIS CONTR. |