Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/20/2001 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 11/20/2001 |
PLUMBING - FINAL |
|
Approved |
1.) ALL CORRECTIONS HAVE BEEN MADE OK 2.)PLUMBING FINAL OK 3.) OK FOR C OF O PENDING VERIFICATION OF CERTIFICATION OF RPBP AND ANY OTHER INSPECTIONS 4. UCC LEFT AT METER. |
| 11/19/2001 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) EXPANSION TANK AND RECIRCULATION PUMP MUST BE SUPPORTED INDEPENDENTLY FROM PIPING. SEE NOTES #3 & 4. ABOVE. MAY NOT BE SUPPORTED BY PIPING OR FITTINGS. |
| 11/16/2001 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) TOILET PAPER DISPENSERS MOVED OK 2.) METAL APPLIANCE CONNECTORS OK 3.) ONE VENT EXTENDED OK CAP OFF ABANDONED VENT IN APPROVED MANNER. 4.) CO AT GAR SINK OK 5.) WATER HEATER CORRECTIONS NOT COMPLETE. |
| 11/15/2001 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) TOILET PAPER DISPENSER REDUCES SIDE CLEARANCE ON HC WATER CLOSET T0 13" NOT APPROVED 2.) TEP RELIEF DRAIN SPLASHES AT FLOOR SINK 3.) SUPPORT RECIRCHLATION PUMP-PIECE OF ABS NOT APPROVED. 4.) UNION AT EXPANSION TANK LEAKS SUPPORT TANK TO WALL 5.) REVIEW TABLE 12-10 CAPACITITES OF METAL APPLIANCE CONNECTORS FOR ROOF TOP UNITS. 6.) VENTS WITHIN 10' OF AIR INTAKE MUST BE EXTENDED AND PAINTED PER INSTALLATION STANDARD 7.) INSTALL APPROVED CLEAN OUT PLUG AND COVER AT BAR SINK. |