Permit: T01CM03125

Parcel: 115211520

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T01CM03125

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
06/06/2002 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
05/13/2002 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*1.) WE CAN NOT USE SHEET METAL SCREWS FOR GROUNDING 250-8. ALSO PLEASE CLEAN UNDER GROUND BAR 250-12. 2.)PLEASE PROVIDE A LETTER ON COMPANY LETTER HEAD VERIFING TORQUE VALVES. 3.) FRONT LIGHT FIXTURES NOT INSTALLED AT THIS TIME. 4.) PLEASE REVISE SERVICE PLANS OR INSTALL AS PER PLANS AND HAVE CITY APPROVALSTAMP. 5.) A BOND WILL NEED TO BE POSTED FOR POWER OR COMPETION OF FINAL. 6.) FINISH SUPPORT WIRES AND ATTACHING FIXTURES TO GRID OK ROOF SUBJECT TO MECHANICAL INSPECTOR.
05/07/2002 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*M/C CABLE IS ALLOWED AS PER 3.8 OF SPECS. OK 2 X 4 LIGHTS IN DINNING ROOM AREA.