Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T01CM03125
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2002 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
| 05/13/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*1.) WE CAN NOT USE SHEET METAL SCREWS FOR GROUNDING 250-8. ALSO PLEASE CLEAN UNDER GROUND BAR 250-12. 2.)PLEASE PROVIDE A LETTER ON COMPANY LETTER HEAD VERIFING TORQUE VALVES. 3.) FRONT LIGHT FIXTURES NOT INSTALLED AT THIS TIME. 4.) PLEASE REVISE SERVICE PLANS OR INSTALL AS PER PLANS AND HAVE CITY APPROVALSTAMP. 5.) A BOND WILL NEED TO BE POSTED FOR POWER OR COMPETION OF FINAL. 6.) FINISH SUPPORT WIRES AND ATTACHING FIXTURES TO GRID OK ROOF SUBJECT TO MECHANICAL INSPECTOR. | |
| 05/07/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*M/C CABLE IS ALLOWED AS PER 3.8 OF SPECS. OK 2 X 4 LIGHTS IN DINNING ROOM AREA. |