Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM03125
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/07/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 05/06/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK PANEL A & B ALSO SWITCH BOX & CONDUIT BY SOUTHGATE DOOR. CHECKED OUT NEU. BOND COLD WATER BOND OK, CONTR. TORQUED BUSS PER MANUF. SPEC'S, SUBMIT LETTER OF TORQUE FOR GEAR, HOUSE PANEL OK LEFT PAPER WORK, REQUIREMENTS FOR TEMP POWER. | |
| 03/20/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK WALLS 1.) PLEASE PROVIDE LETTER AUTHORIZING USE OF M/C CABLE OR INSTALL AS PER PLANS. | |
| 02/21/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*EMT RACEWAY FOR EXTERIOR LIGHTS WALL PACKS EAST & NORTHWALLS. |