Permit: T01CM03122

Parcel: 121100080


Addresses:

4734 E EDISON ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/05/2001 PLUMBING - FINAL Approved IVRS - Inspection 0000*1.) CONTRACTOR CONVINCED INSPECTOR THAT PLUMBING WAS INSTALLED PER 94 UPS. HE PROVIDED DRAWING AND EXPLAINATION CONSISTENT WITH ACCEPTABLE PLUMBING PRACTICES. WATER TEST WAIVED, AND WORK APPROVED. 2.) ALL CORRECTIONS MADE OK.
08/01/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) LAVATORY RE-ROUGHED FOR ADA HOWEVER, IT WAS COVERED BEFORE INSPECTION 2.) REMOVED VANIKY FRONT-AND TESTED BY INSPECTOR WITH A WHEEL CHAIR OK 3.) WATER CLOSET OK 3.) SHOWER OK 5.) NEED INSULATION KIT ON LAV DRAIN. 6.) WILL MEET WITH CONTRACTOR TO DISCUSS HOW TO PROCEED WITH COVERED WORK.
07/22/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.ADA HANDICAPPED WATER CLOSET REQUIRES RIGHT HAND FLUSH HANDLE. 2.) HANDICAPPED SHOWER REQUIRES H.C. SHOWER TRIM INCLUDING SLIDE BAR AND HOSE W/CHECK VALVE 3.) VANITY CONNECTED TO BIDET DRAIN CONSTITUTES DOUBLE TRAPPING. 4.) VANITY DOES NOT MEET ADA REQUIREMENT. RE VOUGH FOR WALL HUNG LAVATORY AND HANG WITH 27" MINIMUM CLEAR UNDERNEATH 34" MAXIMUM TO OVERFLOW.
07/17/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) MUST INSTALL A ADA HANDICAP WATER CLOSET WITH OPEN FRONT SEAT WITH NO LID. 2.) H.C. SHOWER REQUIRES A SLIDE BAR AND SHOWER LOSE WITH CHECK VALUE IN HOSE IF HOSE CAN TOUCH THE FLOOR.