Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
Permit Number - T01CM03118
Inspection Description - MECHANICAL - HOODS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/12/2001 | MECHANICAL - HOODS | Approved | ||
08/30/2001 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection 0000*16 GA. BLK IRON UP THROUGH ROOF W/ FLAME CHECK WRAP, OK . CHECK SHARP EDGES ON S.S. HOOD THIS IS DANGEROUS WHEN CLEANING. | |
08/24/2001 | MECHANICAL - HOODS | Denied | IVRS - Inspection 0999*ON 8/21/01 I LEFT INSPECTION REPORT W/ITEMS LISTED ABOVE. I WANTED TO SEE DUCT AND WRAP PROPERLY EXTENDED UP INTO CURB. I WANT CURL OPENED UP TO INSPECT WORK CONCELED INSIDE CURB UNDER EXHAUST BLOWER! | |
08/21/2001 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection 0000*1.) NEED TO EXTEND 16 GA. BLACK IRON UP INTO CURB AS PER DRAWING. 2.) 3 M FIRE MASTER WRAP MUST CONTINUE 18" MINIMUM ABOVE CUMBUSTIBLE MATERIAL. WANT TO SEE ADDITIONAL WRAP PRIOR TO FINAL SEALING OF HOLES. RATED CHASE/WRAP DOES NOT END AT ROOF SHEETING. |