Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/20/2002 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 02/14/2002 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245*1. ) ALL FOUR SEISMIC CLIPS MUST BE TURNED OUT ON THE 2 X 4 FLOUR. LITING FIXTURES. THE CLIPS MUST HOOK OVER THE TEE BAR. A SINGLE SELF TAPPING SCREW ON EACH END OF THE FIXTURE MAY SUBSTITUTE. 2.) EACH FIXTURE MSUT HAVE A A SEISMIC WIRE ON EACH END OPPOSITE CORNER. 3.) EMERGENCY LIGHTS MUS THAVE ONE SEIESMIC WIRE. 4.) ALL "J" BOXES MUST BE COMPLETED AND COVERED. 5.) 2 X 4 FLOUR. FIXTURES INSTALLED END TO END CAN SHARE THE SEISMIC WIRE. 6.) SUPPORT FIXTURE WHIPS SO THEY DO NOT REST ON THE CEILING GRID OR TILES CORRECT & RECALL. |