Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/23/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*PROVIDE THE PROPER AMOUNT OF BOLTS TO CLOSE THE EXPOSION PROOF SWITCH THEN CALL ME AND I WILL CLEAR POWER. |
| 10/16/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*ARE INSPECTION FEE IS DUE BEFORE NEXT INSP. NEED TO SEE INTERIOR OF YARD. CHANGE PLANS TO REFLECT ACTUAL NO SUB PANEL SEE PLAN. |
| 09/21/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*NOTE: THE UFER COMING FOR THE 2 GROUND RODS HAS TO BE TIED TO THE NEUTRAL, RIGHT NOW IT IS ONLY TIED TO THE ENCLOSURE. THE NEUTRAL BAR DOES HAVE A GREEN SCREW TO THE ENCLOUSURE HOWEVER THE ENCLOSURE CANNOT BE THE ONLY MEANS TO CONNECT THE UFER TO THE NEUTRAL, A MAIN BONDING JUMPER SHALL BE USED 99 NEC 250-24 A-4 AND 250-28 2.) PLEASE PROVIDE INFO ON THIS CABLE BEING ALLOWED TO REST ON GROUND WITH OUT PHYSICAL PROTECTION 3.) BOLT DOWN MAIN DISCONNECT AT UNIT AND SEAL HOLE AT BOTTOM (1/2") |