Inspection Status: Approved
Inspection History: ROOF NAILING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/09/2001 |
ROOF NAILING |
|
Approved |
IVRS - Inspection 0000* |
| 11/06/2001 |
ROOF NAILING |
|
Not ready for Inspection |
IVRS - Inspection 0000*1.) PLAN CALLS FOR 11'8" SPAN CENTER SECTION OF ROOF,YOU HAVE APPROX 13'6". MAXIUM SPAN OF 2 X6 AT 24" OC 15.10'9". YOU NEED TO BE 16"O.C. THAT WILLGET YOU TO 13'2". 2.) ADD EXPANSION ANCHORS TO BOTTOM PLATES AT PLATE JOINTS. REQS. ONE BLOT WITHIN 12" OF ANY JOINT END. |