Permit: T01CM03050

Parcel: 116112580

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
09/06/2001 FRAMING Approved IVRS - Inspection 0000*
09/04/2001 FRAMING Denied IVRS - Inspection 0999*1.) NEED DBL SND AF F-9
TRUSS 2.) FLOOR NOT NAIL 3.) CONNECT ALL GROUNDS 4.) S GARAGE WALL NEED FIRE BLOCK 2 FLOOR. 5.) REPAIR DUCT @ 2 FLOOR.
08/30/2001 FRAMING Denied IVRS - Inspection 0999*1.) SECURE ROMEX THRU OUT 2.) SEAL ELECT. UNDERGROUND CONDUIT 3.) NAIL PROT @ DRYER VENT 4.) PROVIDE ENC. FIX FOR FLOOR TRUSS @ STAIRS 5.) SUB FLOOR NOT SCREWED 6.) FIRE BLK. ARCH 2ND FLOOR FIRST FLOOR 7.) PROVIDE HANGERS @ LANDING 8.) NAIL SHEAR & STAIR 9.) CLIP INT. BRK10.) BLK BETWEEN FLOOR JOISTS @ INT WALL PER PLAN 11.) PROVIDE DETAIL 2 SD 4 @ REAR WALL. 12.) FIRE STOP ENTRY COLUMN.