Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/06/2001 |
ELECTRIC - INTERMEDIATE |
|
Approved |
|
| 07/20/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
STORAGE ONLY ROUGH WALLS APPROVED. EXCEPT PANELBOARD. |
| 07/13/2001 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*OK CEILING EXCEPT STORAGE RM OK WALLS. |
| 07/12/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0245*1.)SUPPORT MC AND EMT PER NEC. 334-10 348-13 2.) INSTALL INSERT BUSHING ON ALL MC TERMINATIONS 300-15-C NEC. TO PROTECT FROM ABRASION OF CONDUCTORS. |