Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T01CM03015
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/24/2001 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection 0000* | |
08/22/2001 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection 0000*/ 1) ADD NAILER ON SOUTH END OF ARCH FOR OSB AND STUCCO 2) NO DRY WALL ON FRONT ENTRY CEILING (THEREFORE YOU NEED BRACING ADD A 2 X4 ON EACH END HALF WAY FROM WALL TO CENTER EXISTING 2 X 4 BRACE, STUCCO WILL NOT HOLD THESE TRUSS CHORDS | |
08/21/2001 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) BLOCK AT OSB CUT FOR ROOF PENETRATIONS (MECH) 2) STIFFEN LARGE ARCH AT FRONT | |
08/16/2001 | EXT METAL CLIPS/EXT SHEATHING | Denied | 1) MISSING NAILING ON ROOF DECK 2) BLOCK OSB RUN IN PARALLEL TO RAFTER 3) ADD WIND BRACE FRONT GARAGE NORTH WALL 4) FRONT ARCH, ADD 2 X 4 VERTICAL INSIDE (OUTSIDE AT WALL WHERE ARCH ATTACHES ADD PANELS TO STIFFEN ARCH AND SHEATH BOTTOM, OR HAVE A DETAIL SUBMITTED THAT WORKS, FOR STUCCO 24" ON CENTER VERTICAL STUDS 5) INSTALL COLLAR TIES AT FRONT GABLE 2 X 6 FIELD FRAME 6) AT SHEAR PANELS FRONT ENTRY, ROOF DECK NOT NAILED, SHEAR PANELS NOT NAILED TO DECK, QUESTION PLAN, CALLS FOR DETAIL 5/DT1 SOLID SHEAR, WHY THE SHEAR PANELS 7) ADD 2 X 4 OUT RIGGERS TO SUPPORT ARCH TO MAIN BOX |