Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T01CM03012
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/12/2001 | ELECTRIC - UNDERGROUND | Approved | ||
11/21/2001 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*1-2 1/2" PVC CONDUIT FROM TEP J-BOX TO SERVICE AT SOUTHEND OF FUEL ISLAND. OK TO COVER SUBJECT TO VERIFICATION OF LISTING BY APPROVED TESTING LAB SUCH AS UL ON CANTEX PVC CONDUIT. SHOULD BE ON PVC. 140' APPROX. 2.) 1" PVC & 3/4" TO SIGN OK 3.) 2-2" PVC STUBS TOWARDS FRY'S STORE FROM SERVICE 15' | |
11/13/2001 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*NOTES OK U.G. FOR DISPENSERS, TANKS, KIOSK, | |
11/09/2001 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection 0245*NOTES CONDUIT AROUND AND BETWEEN DISPENSER AREA MUST BE 24" BELOW FINISHED GRADE PER 300-5 AND ARTICLES 5012 NEC 514. | |
10/25/2001 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*OK STUB UPS FOR CANOPY LTG. AND VIDIO & FUTURE. |