Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 08/15/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 08/13/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) REMOVE SCREEN FROM DRYER VENT 2) PROVIDE LISTING FOR FIXTURES THAT WILL ATTACH AT 3.0 PANCAKE BOXES 3) NAIL PENETRATED ABS WAHSER DRAIN PROTECT AND PROVIDE TEST TO ALL ABS PIPE 10' HEAD TEST 4) SECURE PLATFORM "BUILT UP" FROM LATERAL ROTATION 5) REFRIGERENT LINE DAMAGED BY FHA METAL STRAP 6) IDENTIFY ADDRESS AT PANEL METER SOCKET PER TEP 7) NAIL LADDER BLOCKS AT SHEARWALL TRANSFER 8) ISOLATE PEX FROM FRAMING STRAP 9) FINAL SUBJECT TO APPROVED REVISION AIR DUCT OPENINGS 10) INSTALL 2 X 8 HEADER AT BACK SLIDER |