Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 08/17/2001 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000*/ 1) PROVIDE BRACING AT BOTTOM CHORD OF TRUSS AS PER CALC'S 2) PROVIDE SPECAIL INSPECTION CERTIFICATE FOR HTT, LTT HOLDOWNS BY INTERMEDIATES |
| 08/16/2001 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) MISSING RIDGE BLOCKING IN GARAGE 2) SIMPSON STT2145 NOT INSTALLED INSIDE OF GARAGE 3) POT TO BEAM CONNECTION SUB STANDARD AT BACK PATIO 4) PROVIDE BLOCKING ABOVE LEDGER AT SHEARWALLS PATIO CONNECTION 5) SECURE DOUBLE TOP PLATES NOT CABIN TIED 6) PROVIDE A POSITIVE CONNECTION AT BACK WALL STUD CUT NOT ATTACHED TO DOUBLE TOP PLATE 7) SEE SHEET S1 NEED, SPECIAL INSPECTION FOR LTT & HTT HOLDOWNS PER ICBO ER 5279 |
| 08/15/2001 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE THE FOLLOWING DETAIL 14/DT1 AND 10/DT1 2) SHEAR PANELS 3) RIDGE BLOCKS 4) STT2115 AT GARAGE |