Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM02962
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/26/2001 | ELECTRIC - FINAL | Approved | ||
12/20/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*APPROVED PARTIAL NEED THE SUITE ENERGIZED SO LIVE TEST OF ELECTRICAL PLANT CAN BE CARRIED OUT. | |
12/19/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*INSTALL LABEL ON BREAKER PNL INSIDE AND AT METER SECTION. | |
12/14/2001 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*NOTES 1.) USE LISTED STRAPS FOR MC CABLE, ALSO MUST BE ART 110 NEC SUPPORTED WITHIN 12" EACH TERMINATION, WITH EXCEPTION FOR FIXTURE WHIPS NO LONGER THAN 6' |