Permit: T01CM02962

Parcel: 12108090B


Addresses:

6206 E PIMA ST #02


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM02962

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/26/2001 ELECTRIC - FINAL Approved
12/20/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*APPROVED PARTIAL NEED THE SUITE ENERGIZED SO LIVE TEST OF ELECTRICAL PLANT CAN BE CARRIED OUT.
12/19/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*INSTALL LABEL ON BREAKER PNL INSIDE AND AT METER SECTION.
12/14/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*NOTES 1.) USE LISTED STRAPS FOR MC CABLE, ALSO MUST BE ART 110 NEC SUPPORTED WITHIN 12" EACH TERMINATION, WITH EXCEPTION FOR FIXTURE WHIPS NO LONGER THAN 6'