Permit: T01CM02961

Parcel: 11706187D


Addresses:

260 E CONGRESS ST


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T01CM02961

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/05/2001 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*INSPECTED 7:00 AM NOT READY REINSPECTED 8:15 AM 1.) MAP SINK ROUGH OK 2.) LEAKS REPAIRED OK WATER TEST OK TO 10 FOOT HEAD PRESSURE TEST OK 3.) OK TO COVER WALLS 4.) REVISED APPROVED DRAWING OK 5.) WILL SEE VTR ON ABOVE CEILING INSPECTION.
07/03/2001 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1. FIX LEAK IN VENT 2.) RE ROUGH MOP SINK VENT IS TO BE CONNECTED DOWNSTREAM O FTHE TRAP, WITH THE INVENT TAKER OFF ABOVE THE CENTORLINE OF THE DRAINPIPE OK TO COVER MAIN TRUNK LINE ONLY
06/29/2001 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*PROVIDE APPROVED REVISED PLAN PROVIDE WATER TEST CALL AGAIN. PROVIDE APPROVED BANDS ON SEWER.
06/28/2001 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
06/26/2001 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*NOT TO PLAN PROVIDE APPROVED REVISED PLAN OR INSTALL AS PER PLAN 10 TEST REQUIRED
06/18/2001 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*PLEASE SEE RISER DIAGRAM.
NOT INSTALLED AS PER PLAN AND NOT TO CODE.
PLEASE NOTE LICENSED PLUMBING CONTRACTOR REQUIRED.