Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T01CM02961
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/05/2001 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*INSPECTED 7:00 AM NOT READY REINSPECTED 8:15 AM 1.) MAP SINK ROUGH OK 2.) LEAKS REPAIRED OK WATER TEST OK TO 10 FOOT HEAD PRESSURE TEST OK 3.) OK TO COVER WALLS 4.) REVISED APPROVED DRAWING OK 5.) WILL SEE VTR ON ABOVE CEILING INSPECTION. | |
07/03/2001 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1. FIX LEAK IN VENT 2.) RE ROUGH MOP SINK VENT IS TO BE CONNECTED DOWNSTREAM O FTHE TRAP, WITH THE INVENT TAKER OFF ABOVE THE CENTORLINE OF THE DRAINPIPE OK TO COVER MAIN TRUNK LINE ONLY | |
06/29/2001 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*PROVIDE APPROVED REVISED PLAN PROVIDE WATER TEST CALL AGAIN. PROVIDE APPROVED BANDS ON SEWER. | |
06/28/2001 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* | |
06/26/2001 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*NOT TO PLAN PROVIDE APPROVED REVISED PLAN OR INSTALL AS PER PLAN 10 TEST REQUIRED | |
06/18/2001 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*PLEASE SEE RISER DIAGRAM. NOT INSTALLED AS PER PLAN AND NOT TO CODE. PLEASE NOTE LICENSED PLUMBING CONTRACTOR REQUIRED. |