Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T01CM02943
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/13/2002 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000* | |
| 01/22/2002 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection 0000*CABLE WAS DROPED BEFORE PROJECT STARTED. 1.) CONDUCTOR FOR BATH BAR TO BE MADE UP IN THE BOX ALSO USE AN APPROVED CONNECTOR FOR THE GROUND WIRE. 2.) PLEASE INSTALL CONDUCTORS UNDER TEMANALS AS LISTED AND CORRECTLY DOUBLE TAPPING AND IN A CLOCK WISE DIRECTION. 3.) UNGROUNDED CONDUCTORS TO BE CORRELY IDENTIFIED. 4.) PLEASE LABEL A/C DISCONNECT 5.) FLOURSCENT FIXTURES ARE TO BE GROUNDED ALSO A BUSHING IS REQUIRED TO PROTECT THE CONDUCTORS 6.) INSTALL HOT INSTALLATION INSTRUCTION DO NOT LIST A CORD AS AN APPROVED WIRING METHOD. ALSO A DISCONNECT MEANS IS REQUIRED. 7.) I CANN NOT FIND THE WELDER PLUG ON THE PLANS. I NEED LOAD CALCULATIONS AND RECPTABLE CONFIGURATION FOR INFORMATION 8.) YOU ARE MISSING AN OUTSIDE LIGHT FIXTURE. |