Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/24/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 12/22/2001 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*1.) USE CONNECTIONS AS PER BREAKER LISTING 2.) PLEASE USE ALL STRAND UNDER TERMANAL LUG 3.) PLEASE TIGHTEN LOOSE CONDUIT FITTINGS 4.) CAN NOT USE SHEET METAL SCREW FOR GROUNDING 250-8. 5.) PLEASE PROVIDE WORKING CLEANENCE FOR COOLE BOX 6.)USE APROVED FITTINGS TO ENTER RELAY BOX 7.) GROUNDING ELECTRODE TO BE TERMANATED AT GROUNDED BAR 250-32. 8.) FILL UNUSED OPENINGS. |