Permit: T01CM02923

Parcel: 11515197A


Addresses:

1901 N ORACLE RD 10

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/24/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
12/22/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*1.) USE CONNECTIONS AS PER BREAKER LISTING 2.) PLEASE USE ALL STRAND UNDER TERMANAL LUG 3.) PLEASE TIGHTEN LOOSE CONDUIT FITTINGS 4.) CAN NOT USE SHEET METAL SCREW FOR GROUNDING 250-8. 5.) PLEASE PROVIDE WORKING CLEANENCE FOR COOLE BOX 6.)USE APROVED FITTINGS TO ENTER RELAY BOX 7.) GROUNDING ELECTRODE TO BE TERMANATED AT GROUNDED BAR 250-32. 8.) FILL UNUSED OPENINGS.