Permit: T01CM02923

Parcel: 11515197A


Addresses:

1901 N ORACLE RD 10

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
12/22/2001 ELECTRIC - UNDERGROUND Approved IVRS - Inspection 0000*
11/13/2001 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*OK 1-1 1/4" PVC UNDER ROADWAY.
11/09/2001 ELECTRIC - UNDERGROUND Denied IVRS - Inspection 0999*1.) USE LISTED FOR ELECTRICAL CEMENT TO CONDUITS. 2.) CAN NOT READ 1-LINE DIAGRAM. DOES IT HAVE AN APPROVAL STAMP.
09/12/2001 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*OK CONCRETE ENCASED ELECTRODE UFER PLEASE CHANGE BUILDING NUMBER # ON PERMIT.
09/11/2001 ELECTRIC - UNDERGROUND Denied IVRS - Inspection 0225*CONCRETE ENCLOSED ELECTRODE TO BE 20' LONG 250-50 (C)