Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 08/22/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 08/21/2001 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) FRAMING AND MECHANICAL WILL BE LOOKED AT AGAIN AFTER LINE SET FOR CONDENSOR IS INSTALLED |
| 08/20/2001 |
FRAMING |
|
Denied |
1) HEATER FLUE PIPE NEED 1" CLEARANCE, FROM COMBUSTIBLES 2) FIRE BLOCK AT ENTERANCE 3) PROVIDE AB AT FRONT DOOR 4) SECURE VALVES AT SHOWER, TUBS AND BANG PLATES 5) PROTECT OR MOVE BACK WATER LINE AT MASTER BEDROOM 6) BLOCKING AT RIGHT MAIN VENT AT HALL 7) BLOCK 3 SIDES AT VENT IN KITCHEN 8) REMOVE SCREEN AT DRYER VENT EXIT 9) A/C LINE NOT IN |