Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T01CM02813
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/09/2001 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
10/08/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*WIRING ABOVE CIELING PARTS OK. | |
10/02/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*PARTIAL 1.) WAITING AREA & HALL OK. | |
09/26/2001 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999*1.) FINISH MAKE UP OF CAN LIGHTS. 2.)NEED SUPPORT WIRES ALL LIGHTS/CANS 3.) CANNOT USE CEILING SUPPORT WIRES FOR M/C CABLE OR FIXTURE WHIPS NEED TO BE INDEPENDANT 300-11 4.) SUPPORT CONDUITS AS PER CODE. 5.) OPEN JUNCTION BOXES. | |
08/22/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*1.) CIELING DROP IN LITES OK. | |
08/14/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*DRIVEWAY CLING. OK | |
08/13/2001 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection 0000* |