Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/13/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) INSTALL BREAKER KO BLANK INSIDE & OUTSIDE PANEL.2.) BOX MISSING COVER UNDER FRONT (WEST) CANOPY. 3.) PROVIDE EXT. LADDER FOR ROOF ACCESS TO INSPECT ROOF ELECTRIC. |
| 07/13/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*AFTER HOURS PM INSPECTION FRI 7/13/01 PAID CHECK#37459 (CHESTNUT CONST.) 2090 FINAL ELECTRIC APPROVED 7/13/01 |
| 07/12/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) COMPLETE TRIM OUT 2.) REPAIR & SUPPORT MC CABLE ABOVE PANEL 334-10 NEC. 3.) PENDANT HUNG FIXTURE MUST HAVE SUPPORT OTHER THAN GRID. 300-11 NEC. 4.) UPDATE PANEL SCHEDULE. |