Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 07/06/2001 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 07/05/2001 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245*1.) 1/2 EMT ROOM #134 EAST WALL ABOVE CEILING NOT STRAPPED. (J-BOX). 2.) MC, EMT, RACE WAYS ABOVERESTOOMS AND OUTSIDE WALLS OF RESTROOM NOT SUPPORTED PROPERLY. ELECTRICAL CONTR.NOT ON SITE 3.) CONTRACTOR STILL NOT IN COMPLIANCE WITH SUPPORT. METHODES.4.) BREAKER PANEL COVER OFF WITH EXPOSED LIVE WIRING UNSAFE CONDITION MERITS JOB SHUT DOWN. |
| 07/03/2001 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0935*1.) THIS IS 3RD INSPECTION WITH NO COMPLAINCE TO SUPPORT REQUIREMENT FOR MC CABLE. SEE WRITE UP 6/15/01 INSPECTION 7/2/01 INSPECTION 2.) SUPPORTS FOR MC TO BE WITHIN 12" EACH TERM OR BOX ETC. AND AT 6 INTERVALS 3.) A RE INSPECTION FEE IS ASSESED PLEASE PAY RE INSPECTION FEE 201 N STONE PRIOR TO FUTURE INSPECTIONS. |
| 07/02/2001 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245*1.) SUPPORT EMT CONDUIT PER 348-13 N.E.C. 2.) SUPPORT MC CABLE PER 334-10 N.E.C. 3.) SUPPORT J-BOXES PER 370-23,300-11 N.E.C. |