Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01CM02810

Parcel: 12605146G


Addresses:

1010 N ALVERNON WY

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/18/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
06/15/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*1)MC CABLE TO BE SUPPORTED WITHIN 12" EACH BOX, TO STUDS, NOT EACHOTHOR 334-10 N.E.C.
2)INSERT BUSHING PROVIDED WITH MC CABLE TO PERVENT ABRASION OF CONDUCTORS.AT CABLE ENDS, 300-15.C N.E.C.