Permit: T01CM02801

Parcel: 112040620

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
05/17/2002 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
05/13/2002 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection 0000*/ 1) SEWER DRAIN LINE LESS THAN 12" OF COVER MUST BE IRON 2) PROVIDE CITY OF TUCSON APPROVED DETAIL FOR NORTH 5 X 10 GLU LAM BEAM CONNECTION TO MASONARY WALLS 5) SOUTH GLUE LAM BEAM NOT PROPERLY BEARING OR CONNECTED ON WEST END 6) PROVIDE CITY OF TUCSON APPROVED DETAIL FORA CARPORT FIRE RATING FOR ROOF EXTENTION TO LESS THAN 3 FEET TO PROPERTY LINE 7) DRYER MUST BE 4 WIRE CIRCUIT WITH 4 PRONG OUTLET 8) GROUND ALL METAL ELECTRIC BOXES. REMVOE ALL DEVICES FOR INSPECTION 9) ALL LIGHT SWITCHES MUST BE GROUNDED 10) OK TO DRY IN ROOF
05/07/2002 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0105*/ 1) SET BACKS ARE NOT PER PLAN. YOU MUST PROVIDE PROPERTY PINS ON ALL CORNERS OF PROPERTY AND INSURE LAYOUT IS PER PLAN. IF PLAN AND PROPERTY LINE IS NOT CORRECT ON NEXT INSPECTION YOU WILL BE CHARGED A REINSPECTION FEE
01/16/2002 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection 0000*