Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date |
Description |
Inspector |
Results |
Comments |
| 10/14/2002 |
ELECTRIC - UNDERGROUND |
|
Approved |
IVRS - Inspection 0000* |
| 10/11/2002 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*1.) CANNOT USE SHEETMETAL SCREW FOR GROUNDING 2.) A SEALING DEVICE IS NEEDED FOR ENTRACES ABOVE BUSS. 3.) INSTALL LOCKNUTS CORRECTLY. 4.) NEED CIRCUIT DIRECTORY FILLED IN. |
| 10/08/2002 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*1.) BONDING JUMPERS TO BE SIZED PER 250-102 & 250-66. 2.) GROUNDING ELECTRODE CONDUCTOR TOBE CONNECTED TO GROUNDED TERMANAL 250-24 |
| 07/16/2002 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*OK AS MARKED ON PLAN. |
| 07/02/2002 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000* OK POLE TO POLE TO BUILDING AS MARKED OK POLES BASES (3) A-2 NORTH SIDE |
| 06/20/2002 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*OK POLE TO POLE AS MARKED. |
| 10/23/2001 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*NOTES OK TO CLEAR FOR TEMP CONST. POWER AT TEMP SERVICE #1. |
| 10/15/2001 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*OK 6-2 1/2" PVC UNDER SLAB. 6 -2" |