Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T01CM02788

Parcel: 13419042C


Addresses:

7204 E BROADWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/30/2001 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
08/28/2001 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*1.) MAKE FILTER COVER ACCESSABLE COVERED W/FLEX DUCT CONNECTOR. 2.) PAINT PVC.
08/23/2001 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1.) PROVIDE VENT CAP ON A/C UNIT 2.) PROVIDE TRAP ON CONDENSATE DRAINS 3.) MOVE VENT TO DOWNSTREAM OF TRAP. 4.) USE AGA APPROVED GAS VALVES 5.) COVER CANVERS CONNECTORS. 6.) REPAIR BROKEN SEAT TITE. 7.) PROVIDE AN OUTSIDE AIR VENT ON AC UNIT.