Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date |
Description |
Inspector |
Results |
Comments |
| 08/02/2001 |
ELECTRIC - UNDERGROUND |
|
Approved |
IVRS - Inspection 0000*U/G OK CHECK W/TEP FOR TRENCH, BEFORE BACKFILLING. SERVICE EQUIPMENT NOTES: 1.) TWO WIRES INTO A SINGLE LUG FOR GROUNDS IS NOT PERMITTED. 2.) THE TWO PIECE GROUND CLAMPS ARE NOT DESIGNED TO "PINCH" CLAMP WIRE ON PIPES. RECONNECT GROUND WIRE AT COLD WTR & GAS LINES. THANK RECALL. |