Permit: T01CM02786

Parcel: 107070200

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/23/2001 ELECTRIC - FINAL Approved
10/19/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) USE APPROVED BREAKERS FOR PANEL - BREAKERS HAVE BEEN MODIFIED TO FIT NOT ALLOWED. 2.) NEED DISCONNECTING MEANS FOR INSTA HOT WATER HEATERS 3.) NEED EXTEND RING AT OUTLET IN TILE WORK 4.) WORKING CLEARANCE INFRONT OF A/C DISCONNECT 5.) LABEL A/C DISCONNECTS AND COOLER DISCONNECTS 6.) SECURE AND STRAP SEAL TITE CONDUIT. 7.) LOOSE FITTINGS SEALTITE 8.) COOLERS NOT HOOKED UP AT THIS TIME. 9.) PROTECT SEATITE WHERE PASSING THROUGH METAL. 10.) WEATHER PROOF COVERS TO BE FOR CONTINOUS USEAGE.
10/18/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
10/17/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
10/04/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) PLEASE IDENTIFY PANEL WITH HIGH LEG MARKING ON OUTSIDE OF PANEL2.) REMOVE AND BLANK ALL SINGLE PHASE BREAKERS FROM HIGH LEG "B" PHASE IN PANEL BOARD 3.) FINISH ELECTRIC INSTALLATIONS OK TO CLEAR FOR POWER AND TESTING CALLED JUDY.
09/26/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*