Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T01CM02762
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/10/2001 | BUILDING - FINAL | Approved | IVRS - Inspection 0000* | |
10/08/2001 | BUILDING - FINAL | Not ready for Inspection | 1) MINIMUM CIRCUIT AMPACITY 26 AMPS HVAC EQUIPMENT GARAGE MAXIMUM FUSE 30 AMP, 20 AMP INSTALLED TO SMALL 2) HVAC EQUIPMENT NORTH SIDE LIQUID TIGHT, MAXIMUM LENGTH 6', USE RIDGID AND SECURE, CONDUIT AT PRESENT NOT SECURED |