Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 09/04/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 08/30/2001 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) SHEAR PANELS NOT NAILED TO SHEAR WALL BELOW USE STUD TIES 2) CONDENSATE NOT STRAPED/BLOCKED 3) REMOVE SCREWS FROM DRYER DUCT 4) NEED ENGINEERS (DETAIL) REF=SHEAR 5) BLOCK STRAP HOT/COLD AT WATER HEATER 6) REMOVE ROMEX AT PENINSULAR 7) GAS PRESSURE TEST-OK |
| 08/21/2001 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) LIQUID NAIL BLOCKS TO ROOF DECK NEXT TO SHEAR PANELS 2) AT STUD CLIPS TO SHEAR PANEL CORNERS WHERE SHEATHIN IS NOT CONTINOUS (TYP) AND BLOCK IN BETWEEN 3) NAIL VERTICAL MEMBERS TOGETHER |