Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T01CM02756
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/06/2002 | BUILDING - FINAL | Approved | IVRS - Inspection 0000* | |
02/27/2002 | BUILDING - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) TIGHTEN CONNECTION SUB-PANEL TO MAIN DISCONNECT. IF YOU CAN'T, NEED A BONDING JUMPER 3) BOND NEUTRAL BUSS TO CAN 3) NOTE: A/C UNITS ARE BEING FED FROM A 2 POLE 70 AMP BREAKER WITH #6 WIRE 4) NEW A/C IS A 15 AMP REQUIRED CIRCUIT OLD IS 30 AMP WIRE, CHECK FUSES IN BATH FOR CORRECT OVER CURRENT PROTECTION SEE U. L LABELS 5) PUT LOW VOLTAGE WIRE IN CONDUIT, SPLICE IN A BOX, SECURE A/C WHIP | |
01/14/2002 | BUILDING - FINAL | Denied | IVRS - Inspection 0999* |