Permit: T01CM02756

Parcel: 123111160


Addresses:

1438 E LINDEN ST


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T01CM02756

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/06/2002 BUILDING - FINAL Approved IVRS - Inspection 0000*
02/27/2002 BUILDING - FINAL Partial Approval IVRS - Inspection 0000*/ 1) TIGHTEN CONNECTION SUB-PANEL TO MAIN DISCONNECT. IF YOU CAN'T, NEED A BONDING JUMPER 3) BOND NEUTRAL BUSS TO CAN 3) NOTE: A/C UNITS ARE BEING FED FROM A 2 POLE 70 AMP BREAKER WITH #6 WIRE 4) NEW A/C IS A 15 AMP REQUIRED CIRCUIT OLD IS 30 AMP WIRE, CHECK FUSES IN BATH FOR CORRECT OVER CURRENT PROTECTION SEE U. L LABELS 5) PUT LOW VOLTAGE WIRE IN CONDUIT, SPLICE IN A BOX, SECURE A/C WHIP
01/14/2002 BUILDING - FINAL Denied IVRS - Inspection 0999*