Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01CM02755

Parcel: 111030110


Addresses:

3420 N DODGE BL #A

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
06/14/2001 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*1)SOIL WATER TEST OK.2)P.O.C. OF NEW BUILDING DRAIN TO EXISITING BUILDING DRAIN OK.3)OK FOR BACKFILL.4)ALL CORRECTIONS HAVE BEEN MADE.
06/11/2001 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*1)MUST PROVIDE 10' HEAD FOR WATER TEST ON SOIL.2)MUST GYPOSE P.O.C. OF NEW BUILDING DRAIN TO EXISTING BUILDING DRAIN OR SEWER.3)CAN NOT WET VENT WITH COMBO FUR P-3 SINK.ALSO PLAN DOSE NOT SHOW WET VENT.SIZE OF BARRAL TO SMALL.