Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01CM02747

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/10/2001 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
11/29/2001 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*COND. PIPING UMC 1994 & UPC IN AGREEMENT SEC. 310.2. 3/4 PIPING GOOD FOR UP TO 20 TONS. "20/40 TONS." UNITS HAVE 1" NOZZLES PIPING IS NOT REDUCED TO LESS THAN DISCHARGE FOUND ON UNIT.
11/21/2001 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1.) CONDENSATE DRAIN MUST BE THE SAME SIZE AS THE OUTLET ON THE UNIT TH ENTIRE LENGTH AC-3 2.) PLANS CALL FOR ECONOMIZERS PLEASE PROVIDE AS PER PLANS. 3.) PERMANENTLY LABEL EQUIPMENT ON ROOF. 4.) TRAPS ON CODNENSATE DRAINS NOT BUILT PROPERLY. 5.) REPAIR EXHAUST FAN IN MENS ROOM PROVIDE DUCT SMOKE DETECTORS AS PER PLAN. RECALL FOR FINAL INSPECTION.