Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/10/2001 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 11/29/2001 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*COND. PIPING UMC 1994 & UPC IN AGREEMENT SEC. 310.2. 3/4 PIPING GOOD FOR UP TO 20 TONS. "20/40 TONS." UNITS HAVE 1" NOZZLES PIPING IS NOT REDUCED TO LESS THAN DISCHARGE FOUND ON UNIT. |
| 11/21/2001 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) CONDENSATE DRAIN MUST BE THE SAME SIZE AS THE OUTLET ON THE UNIT TH ENTIRE LENGTH AC-3 2.) PLANS CALL FOR ECONOMIZERS PLEASE PROVIDE AS PER PLANS. 3.) PERMANENTLY LABEL EQUIPMENT ON ROOF. 4.) TRAPS ON CODNENSATE DRAINS NOT BUILT PROPERLY. 5.) REPAIR EXHAUST FAN IN MENS ROOM PROVIDE DUCT SMOKE DETECTORS AS PER PLAN. RECALL FOR FINAL INSPECTION. |