Inspection Status: Approved
Inspection History: PLUMBING - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/18/2001 |
PLUMBING - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 11/15/2001 |
PLUMBING - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999*1.) NO CORRECTIONS MADE SINCE LAST INSPECTION REMEMBER WORK MUST BE READY AT THE TIME OF CALLING IN INSPECTION OR YOU RISK PAYING A RE INSPECTION FEE 2.) ROOF DRAIN HANGERS HAVE BEEN DISCONENCTED ADJUST ALL ROOF DRAIN HANGERS SOT THAT THEY SUPPORT THE PIPING. 3.) WATER HEATER NOT INSTALLED. |
| 10/31/2001 |
PLUMBING - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999*1.) GAS PRESSURE TEST OK 2.) ROOF DRAIN WATER TEST OK ZUPPER 2 UPPER DRAINS (MOST EAST) NEED HANGERS SHEETROCK NOT APPROVED SUPPORT. 3.) WATER HEATER ABOVE CEILING NOT INSTALLED |
| 10/29/2001 |
PLUMBING - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999*1.) NO PRESSURE TEST ON GAS USE CORRECT GUAGE. 2.) SUPPORT COPPER AND ROOF DRAINS VERTICALLY IN WALLS, CORRECT BACK PITCH ON ROOF DRAIN OUTLET. 3.) NO WATER TEST ON ROOF DRAINS. |