Permit: T01CM02747

Inspection Status: Approved

Inspection History: PLUMBING - ABOVE CEILING

Date Description Inspector Results Comments
11/18/2001 PLUMBING - ABOVE CEILING Approved IVRS - Inspection 0000*
11/15/2001 PLUMBING - ABOVE CEILING Denied IVRS - Inspection 0999*1.) NO CORRECTIONS MADE SINCE LAST INSPECTION REMEMBER WORK MUST BE READY AT THE TIME OF CALLING IN INSPECTION OR YOU RISK PAYING A RE INSPECTION FEE 2.) ROOF DRAIN HANGERS HAVE BEEN DISCONENCTED ADJUST ALL ROOF DRAIN HANGERS SOT THAT THEY SUPPORT THE PIPING. 3.) WATER HEATER NOT INSTALLED.
10/31/2001 PLUMBING - ABOVE CEILING Denied IVRS - Inspection 0999*1.) GAS PRESSURE TEST OK 2.) ROOF DRAIN WATER TEST OK ZUPPER 2 UPPER DRAINS (MOST EAST) NEED HANGERS SHEETROCK NOT APPROVED SUPPORT. 3.) WATER HEATER ABOVE CEILING NOT INSTALLED
10/29/2001 PLUMBING - ABOVE CEILING Denied IVRS - Inspection 0999*1.) NO PRESSURE TEST ON GAS USE CORRECT GUAGE. 2.) SUPPORT COPPER AND ROOF DRAINS VERTICALLY IN WALLS, CORRECT BACK PITCH ON ROOF DRAIN OUTLET. 3.) NO WATER TEST ON ROOF DRAINS.