Permit: T01CM02747

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
08/09/2001 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*1.) ABS UNDERGROUND OK TO OUTSIDE BLDG. 2.) WATER TEST OK 3.) OK TO BACKFILL.
08/08/2001 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*1.) THE POINT OF VENT, ON A TRAPARM, MAY NOT BE BELOW THE WEIR OF THE TRAP (NO OFFSET ON TRAP ARM) 2.) A DOUBLE SANTEE MAY BE USED AS A DOUBLE FIXTURE FITTING IF THE BARREL OF THE FITTING IS TWO PIPE SIZES LARGER THAN THE LARGEST INLET.