Permit: T01CM02747

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
11/08/2001 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection 0000*
10/29/2001 ELECTRIC - TEMPORARY SERVICE Not ready for Inspection IVRS - Inspection 0000*NOTES 1.) WATER BOND UNDERSIZED. SEE PLAN 2.) PROTECT WATER BOND CONDUCTOR UP TO 8' BOND, GAS, BLD, STEEL PER 250-104 NEC. 3.) NEED TO COMPLETE WIRING AT SERVICE. 4.) SUPPORT MC CABLE PER 334-10 N.E.C. IN SOFFITS COMPLETE WIRING.