Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/23/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
|
| 11/06/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 11/02/2001 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*NOT REQUIRED JERRY ORTA MADE INSPECTION 11/1/01 |
| 11/01/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*SERVICE INSPECTION 1.) NEED ACCURATE CITY APPROVED REVISION FOR SERVICE EG. NO BUS BAR IN GUTTER, DELETED ONE SPARE 4" SERVICE LATERAL. 2.) NEED PROPER CITY APPROVED FAULT CURRENT VALUES AND MAKE NECESSARY CHANGES TO FUSING, ETC. (IF APPLICABLE). NOTE: FOR CONSTRUCTION ONLY POWER WILL NEED EXTERIOR GFI. |
| 10/30/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*NOTE FRONT EXTERIOR ROUGH APPROVED. 1.) PERMANETLY LABEL ALL DISCONNECTS 2.) EMT PROTECTED GROUNDING CONDUCTORS MUST BE BONDED AT BOTH ENDS. 3.) MULTIPLE CONNECTIONS UNDER LUGS THAT ARE ONLY RATED FOR ONE CONDUCTOR 4.) ACCURATELY HAVE CITY APPROVED REVISION AT SITE FOR SERVICE . 5.) PLEASE MOVE 206 AMP DISCONNECT TO HAVE PROPER HAND ACCESS FOR DISCONNECT HANDLE. 6.) SUPPLY SIDE BOND JUMPERS UNDERSIZED. 7.) PROVIDE FAULT CURRENT VALUE PER NOTE. 8.) SPARE 4" CONDUIT NOT INSTALLED. |
| 10/24/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*COMPLETE WALLS. |
| 10/12/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*NOTES OK WALLS EXCEPT, BATHROOMS AND MILLWORK BY OFFICE. |