Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/14/2002 |
MECHANICAL - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000*OK FOR CEILING TILES. |
| 02/12/2002 |
MECHANICAL - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999*CENTER DRAIN PANS UNDER AIR HANDERS CORRECTLY. RUN OVERFLOW DRAINS TO A CONSPICUOUS LCOATION. 2.) INSTALL FUSES IN ELEC. DISCONNECTS 3.) LABEL AIR HANDLERS 4.) PLANS SHOW HUMIDIFIERS ON AIR HANDLERS 5.) PROVIDE SERVICE PLATFORM FOR FITLER ACCESSS ON FC-3 |
| 01/25/2002 |
MECHANICAL - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999*OPEN SHEET ROCK OVER HARD LIDS FOR INSPECTION ON DUCTS. OPEN CHASE FOR INSPECTION ON FIREPLACE FLUE. AIR HANDLER OVER RESTROOM HAS SERVICE PANELS BLOCKED ACCESS OPENINGS NOT LARGE ENOUGH. |
| 01/24/2002 |
MECHANICAL - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999*NO APPROVED PLANS ON SITE. |