Permit: T01CM02726

Parcel: 109250390

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
02/14/2002 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*OK FOR CEILING TILES.
02/12/2002 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection 0999*CENTER DRAIN PANS UNDER AIR HANDERS CORRECTLY. RUN OVERFLOW DRAINS TO A CONSPICUOUS LCOATION. 2.) INSTALL FUSES IN ELEC. DISCONNECTS 3.) LABEL AIR HANDLERS 4.) PLANS SHOW HUMIDIFIERS ON AIR HANDLERS 5.) PROVIDE SERVICE PLATFORM FOR FITLER ACCESSS ON FC-3
01/25/2002 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection 0999*OPEN SHEET ROCK OVER HARD LIDS FOR INSPECTION ON DUCTS. OPEN CHASE FOR INSPECTION ON FIREPLACE FLUE. AIR HANDLER OVER RESTROOM HAS SERVICE PANELS BLOCKED ACCESS OPENINGS NOT LARGE ENOUGH.
01/24/2002 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection 0999*NO APPROVED PLANS ON SITE.