Inspection Status: Partial Approval
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/03/2001 |
BUILDING - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 10/03/2001 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) OFFICE SPACE CANNOT HAVE B/BOARD HTR. ON LIGHTING CIRCUIT, NON HABITAL SPACE IE., OUTLET SPACING 2) FINISH SINK AND DISPOSAL INSTALL |
| 06/18/2001 |
BUILDING - FINAL |
|
Not ready for Inspection |
1) ALL WORK COVERED 2) WASHER ROOM NEEDS A CLEAN OUT ON VERTICAL DRAIN GOING TO VENT 3) ALL BOXES THAT WERE EXTENDED, CANNOT HAVE A SPLICE BOX BURIED IN THE WALL 4) COOLER INSTALLED BY G&A REFRIGERATION WITHOUT PERMIT OR INSPECTION CONDUIT INSTALL NOT DONE IN A WORKMANSHIP MANNER, DISCONNECT NOT SECURED ON ROOF, OPEN DISCONNECT EXPOSE WIRING, IDENTIFY WIRES AT SERVICE PANEL, INSTALL BOX FOR ROTARY SWITCH 5) WILL CHECK WITH SUPERVISOR AS TO WHAT WILL BE REQUIRED TO VERIFY ALL COVERED WORK 6) DISHWASHER DISPOSAL TO BE ON SEPERATE CIRCUIT 7) USE TREATED PLATE FOR SUPPORTING CONDUIT 8) LOCATE DAMPER FOR COOLER |