Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T01CM02717
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/15/2001 | FRAMING | Approved | IVRS - Inspection 0000* | |
08/14/2001 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) REPITCH NEGATIVE MASTER LAV. ARM | |
08/10/2001 | FRAMING | Denied | IVRS - Inspection 0999*1.) "B" VENT REQUIRE MIN 1" CLEARANCE FROM COMBUSTIBLES 2.) CONDENSATE DRAINS MUST HAVE CONTINUOUS FALL 3.) A/C REGISTERS MUST BE BLOCKED FOR SUPPORT 4.)NO TEST ON GAS LINE. 5.) STUDS OVER DRILLED AT REAR BEARING WALL 6.) ROMEX MUST BE STAPLED AT EACH BOX 7.) ROMEX MUS TNOT BE STAPLED ON EDGE. STOPPED INSP. |