Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM02641
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/23/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
05/22/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK 3RD FLOOR RAMP. | |
05/17/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK BRANCH CIRCUITING IN CONCRETE SLABS 1ST & 2ND LEVEL SOUTH HALF. | |
05/15/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245*NOTES PVC CONDUIT MUST BE ENCASED WITH NOT LESS THAN 2" CONCRETE. 300-5 NOTE 2 NEC. |