Permit: T01CM02625

Parcel: 130050030

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
03/21/2002 FRAMING Approved IVRS - Inspection 0000*
03/19/2002 FRAMING Partial Approval IVRS - Inspection 0000*PROVIDE LITERATURE ON FIRE CAULKING NEED DRAFT STOP OR PACK INSULATION.
03/18/2002 FRAMING Partial Approval IVRS - Inspection 0000*1.) PENETRATIONS THROUGH FIRE WALL MUST BE DONE USING APPROVED FIRE BARRIER SYSTEM. PROVIDE SYSTEM & INSTALL ACCORDINGLY. SPACKLE & TAPE IS NOT AN APPROVED SYSTEM. 2.) HAS ROOF NAILING BEEN INSPECTED IT HAS NOT BEEN APPROVED ON PERMIT. 3.) PROVIDE DRAFT STOP @ SOFFIT BY ELECTRIC PANEL. (MINERAL WOOL BATTING MAY BE USED.)