Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/03/2003 | PLUMBING - INTERMEDIATE | Approved | 1.) ABS DWV THRU ROOF OK COPPER WATER OK. CLOSET FLANGES OK TUBS OK. 2.) NOW IS OK TO COVER WALLS. |
|
| 01/29/2003 | PLUMBING - INTERMEDIATE | Cancelled | IVRS - Ri canceled | |
| 01/28/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*/ 1) NOT INSTALLED PER APPROVED PLAN. REDLINE REVISIONS ARE NOT APPROVED UNTIL STAMPED BY PLAN EXAMINER HIAT: INDIRECT WASTE RECEPTOR USED INFREQUENTLY REQUIRES TRAP PRIMER. DO NOT COVER! UNTIL INSPECTED AND APPROVED, THIS INCLUDES INSULATION. NO GAS ON THIS PROJECT | |
| 01/26/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1.) PLEASE POST YOUR ADDRESS AND SUITE NUMBERS 2.) WOOD SHIMS NOT APPROVED STRAPPING. 3.) MINIMUM 2 PIPE DIAMETERS BETWEEN WEIR OF TRAP AND POINT OF VENT. 4.) WHAT IS 2" TRAP ARM BEHIND WATER HEATER? 5.) NO GAS INSTALLED AT THIS TIME. |
|
| 01/22/2003 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* |