Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T01CM02589
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/03/2002 | ELECTRIC - ABOVE CEILING | Approved | ||
| 02/06/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999*1.) FLEX, M/C CABLE, & CONDUIT NEED TO BE SUPPORTED AS PER CODES 300-11,334,336,348 3.) TRAC LIGHTING NEED TO BE SUPPORTED Z(BOX IS SUPPORTED. | |
| 01/16/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*1.) FLEX CONDUIT TO BE SUPPORTED AS PER CODE 300-11 & 350. 2.) SUPPORT CONDUIT AS PER CODE 348. 3.) PLEASE OPEN TILE AROUND FIXTURE FOR INSPECTION OF CLIPS WHEN USING CLIPS PROVIDED WITH THE FIXTURE THEY NEED TO BE SECURELY FATENING THE FIXTURE. 4.) MISSING JUNCTION BOX COVERS 5.) INSTALL NM CABLE AS PER CODE. 6.) WHERE ARE THE CONNECTIONS FOR THE HOOD LIGHTING. | |
| 08/19/2001 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999* |