Permit: T01CM02583

Parcel: 136290840


Addresses:

4730 S ALMOND ST


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T01CM02583

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/11/2001 BUILDING - FINAL Approved IVRS - Inspection 0000*
06/08/2001 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) NO ONE ON SITE, CALLED 886-9291 THREE TIMES, BUSY 2) RE-CALL INSPECTION AND ARRANGE FOR ADULT TO BE AT INSPECTION
06/05/2001 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) WIRING RUN IN WHITE PVC MISSING BUSHINGS AND CORRECT FITTINGS, USE ONLY SCHEDULE 80 ELECTRICAL CONDUIT 2) ALUMINUM AWNING ON WEST SIDE YARD, NOT ON PLAN GOES TO PROPERTY LINE 3) WOOD SIDING YOU NEED 6" TO EARTH SOUTH SIDE 4) T&P LINE REDUCED GOING TO OUTSIDE NEED FULL SIZED 3/4" WITH A 90 DEGREE ELBOW 5) DRYER VENT TO BE ALL METAL